Skip to content
Fencer Intel
high 8.5

CVE-2011-4879 in the critical feed json

miniweb.exe in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Up…

published 2012-02-03 14 y ago modified 2026-06-16 4 mo ago also EUVD-2011-4796

cvss
8.5
version 2.0, NVD
cisa kev
Not listed
not in CISA's catalog
epss
12.1%
EPSS 12.1% chance of exploitation in 30 days, percentile 96%
public exploits
1
Exploit-DB

Summary

miniweb.exe in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime does not properly handle URIs beginning with a 0xfa character, which allows remote attackers to read data from arbitrary memory locations or cause a denial of service (application crash) via a crafted POST request.

Vendor advisories

What the vendors themselves say about their products: affected, fixed or not affected, and what to do.

cisa ICSA-12-030-01A updated cvss 8.5

Siemens SIMATIC WinCC Vulnerabilities

  • Siemens Multiple SIMATIC HMI panels (TP, OP, MP, Comfort Panels, Mobile Panels) Siemens WinCC flexible 2004, 2005, 2007, 2008 Siemens WinCC flexible Runtime Siemens WinCC V11 (TIA portal) Siemens WinCC V11 Runtime Advanced
    affected: mitigation “WinCC V11 (TIA Portal) SP2 Update 1, (http://support.automation.siemens.com/WW/view/en/58112587)”

From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf

Timeline

  1. First public exploit (EDB-18166)
  2. Published

Exploit prediction

12.11% chance of exploitation in the next 30 days, higher than 96% of all scored CVEs (FIRST EPSS, 2026-11-09).

Exploits and checks

  • EDB-18166 Siemens SIMATIC WinCC Flexible (Runtime) - Multiple Vulnerabilities dos, 2011-11-28

CVSS scores

assigned by version score vector
NVD 2.0 8.5 AV:N/AC:L/Au:N/C:P/I:N/A:C

Classification

Weakness
  • CWE-20 Improper Input Validation

References

Sources

Fencer Intel keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.