Skip to content
Fencer Intel
medium 4.3

CVE-2012-4356 json

Multiple directory traversal vulnerabilities in Sielco Sistemi Winlog Pro SCADA before 2.07.17 and Winlog Lite SCADA before 2.07.17 allow r…

published 2012-08-19 14 y ago modified 2026-06-16 4 mo ago also EUVD-2012-4299

cvss
4.3
version 2.0, NVD
cisa kev
Not listed
not in CISA's catalog
epss
27.4%
EPSS 27.4% chance of exploitation in 30 days, percentile 98%
public exploits
2
Metasploit, Exploit-DB

Summary

Multiple directory traversal vulnerabilities in Sielco Sistemi Winlog Pro SCADA before 2.07.17 and Winlog Lite SCADA before 2.07.17 allow remote attackers to read arbitrary files via port-46824 TCP packets specifying a file-open operation with opcode 0x78 and a .. (dot dot) in a pathname, followed by a file-read operation with opcode (1) 0x96, (2) 0x97, or (3) 0x98.

Vendor advisories

What the vendors themselves say about their products: affected, fixed or not affected, and what to do.

cisa ICSA-12-213-01A updated cvss 4.3

Sielco Sistemi Winlog Multiple Vulnerabilities

  • Sielco Sistemi Winlog Lite SCADA <2.07.18. Sielco Sistemi Winlog Pro SCADA <2.07.18
    affected: mitigation

From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf

Timeline

  1. First public exploit (EDB-19409)
  2. Published

Exploit prediction

27.38% chance of exploitation in the next 30 days, higher than 98% of all scored CVEs (FIRST EPSS, 2026-11-09).

Exploits and checks

CVSS scores

assigned by version score vector
NVD 2.0 4.3 AV:N/AC:M/Au:N/C:P/I:N/A:N

Classification

Weakness
  • CWE-22 Improper Limitation of a Pathname to a Restricted Directory

References

Sources

Fencer Intel keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.