Skip to content
Fencer Intel
high 7.8

CVE-2012-4713 json

Integer signedness error in RNADiagnostics.dll in Rockwell Automation FactoryTalk Services Platform (FTSP) CPR9, CPR9-SR1, CPR9-SR2, CPR9-S…

published 2013-04-18 13 y ago modified 2026-06-16 4 mo ago also EUVD-2012-4638

cvss
7.8
version 2.0, NVD
cisa kev
Not listed
not in CISA's catalog
epss
3.2%
EPSS 3.2% chance of exploitation in 30 days, percentile 88%
public exploits
0
none known

Summary

Integer signedness error in RNADiagnostics.dll in Rockwell Automation FactoryTalk Services Platform (FTSP) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (service outage or RNADiagReceiver.exe daemon crash) via UDP data that specifies a negative integer value.

Vendor advisories

What the vendors themselves say about their products: affected, fixed or not affected, and what to do.

cisa ICSA-13-095-02A updated cvss 7.8

Rockwell Automation FactoryTalk and RSLinx Vulnerabilities

  • Rockwell Automation FactoryTalk Services Platform and RSLinx Enterprise CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3
    affected: mitigation rockwellautomation.custhelp.com

From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf

Exploit prediction

3.22% chance of exploitation in the next 30 days, higher than 88% of all scored CVEs (FIRST EPSS, 2026-11-09).

CVSS scores

assigned by version score vector
NVD 2.0 7.8 AV:N/AC:L/Au:N/C:N/I:N/A:C

Classification

Weakness

References

Sources

Fencer Intel keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.