CVE-2018-13813 json
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15 Update 4), SIMATIC HMI Comfort Outdoor Panel…
published 7y ago modified 4mo ago also EUVD-2018-5749
- cvss
- 8.1
- version 3.0, NVD
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 1.7%
- EPSS 1.7% chance of exploitation in 30 days, percentile 77%
- public exploits
- 0
- none known
Summary
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15 Update 4), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15 Update 4), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15 Update 4), SIMATIC WinCC Runtime Advanced (All versions < V15 Update 4), SIMATIC WinCC Runtime Professional (All versions < V15 Update 4), SIMATIC WinCC (TIA Portal) (All versions < V15 Update 4), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). The webserver of affected HMI devices may allow URL redirections to untrusted websites. An attacker must trick a valid user who is authenticated to the device into clicking on a malicious link to exploit the vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
Is CVE-2018-13813 in your stack? Fencer shows which of your repositories are affected as soon as an advisory lands, and opens the fix as a pull request.
Check with FencerVendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-18-317-08 updated cvss 6.5
Siemens SIMATIC Panels
-
Siemens SIMATIC HMI Classic Devices - TP/MP/OP/MP Mobile Panel (incl. SIPLUS variants)affected: mitigation
-
Siemens SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants) <V15_Update_4 Siemens SIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants) <V15_Update_4 Siemens SIMATIC HMI KTP Mobile Panels KTP400F KTP700 Siemens SIMATIC WinCC (TIA Portal) <V15_Update_4 Siemens SIMATIC WinCC Runtime Advanced <V15_Update_4 Siemens SIMATIC WinCC Runtime Professional <V15_Update_4affected: fixed in V15, mitigation
Facts from CISA's republication of the vendor's own advisory (CSAF); the linked advisory is the authoritative source. CISA notification · csaf
Exploit prediction
1.68% chance of exploitation in the next 30 days, higher than 77% of all scored CVEs (FIRST EPSS, 2026-11-09).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| NVD | 3.0 | 8.1 | CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:N |
| NVD | 2.0 | 5.8 | AV:N/AC:M/Au:N/C:P/I:P/A:N |
Affected products
- Siemens AG SIMATIC HMI Comfort Panels 4" - 22", SIMATIC HMI Comfort Outdoor Panels 7" & 15", SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F, SIMATIC WinCC Runtime Advanced, SIMATIC WinCC Runtime Professional, SIMATIC WinCC (TIA Portal), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel)
Classification
- Weakness
-
- CWE-601 URL Redirection to Untrusted Site
References
-
cert-portal.siemens.com
/productcert/pdf/ssa-233109.pdf
vendor-advisory
-
securityfocus.com
/bid/105922
vdb-entry, third-party-advisory