CVE-2018-4838 json
A vulnerability has been identified in EN100 Ethernet module IEC 61850 variant (All versions < V4.30), EN100 Ethernet module DNP3 variant (…
published 2018-03-08 8 y ago modified 2026-06-17 4 mo ago also EUVD-2018-16624
- cvss
- 7.5
- version 3.0, NVD
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 1.4%
- EPSS 1.4% chance of exploitation in 30 days, percentile 72%
- public exploits
- 0
- none known
Summary
A vulnerability has been identified in EN100 Ethernet module IEC 61850 variant (All versions < V4.30), EN100 Ethernet module DNP3 variant (All versions < V1.04), EN100 Ethernet module PROFINET IO variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module IEC 104 variant (All versions < V1.22). The web interface (TCP/80) of affected devices allows an unauthenticated user to upgrade or downgrade the firmware of the device, including to older versions with known vulnerabilities.
Patch / fix
- siemens en100_ethernet_module_iec_61850_firmware 4.30
Vendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-18-067-02 updated cvss 7.5
ICSA-18-067-02_Siemens SIPROTEC 4, SIPROTEC Compact, and Reyrolle Devices using the EN100 Ethernet Communication Module Extension (Update B)
-
Siemens EN100 Ethernet module DNP3 variant < 1.04 Siemens EN100 Ethernet module IEC 104 variant < 1.22 Siemens EN100 Ethernet module IEC 61850 variant < 4.30 Siemens EN100 Ethernet module Modbus TCP variant Siemens EN100 Ethernet module PROFINET IO variantaffected: mitigation “EN100 Ethernet module IEC 61850 variant (All versions prior to v4.30): Update to v4.30, which can be located here: https://support.industry.siemens.com/cs/us/en/view/109745821” support.industry.siemens.com
From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf
Exploit prediction
1.40% chance of exploitation in the next 30 days, higher than 72% of all scored CVEs (FIRST EPSS, 2026-11-09).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| NVD | 3.0 | 7.5 | CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N |
| NVD | 2.0 | 5.0 | AV:N/AC:L/Au:N/C:N/I:P/A:N |
Affected products
- Siemens AG EN100 Ethernet module IEC 61850 variant
- Siemens AG EN100 Ethernet module DNP3 variant
- Siemens AG EN100 Ethernet module PROFINET IO variant
- Siemens AG EN100 Ethernet module Modbus TCP variant
- Siemens AG EN100 Ethernet module IEC 104 variant
Classification
- Weakness
-
- CWE-306 Missing Authentication for Critical Functionality
References
-
cert-portal.siemens.com
/productcert/pdf/ssa-845879.pdf
patch, vendor-advisory
-
securityfocus.com
/bid/103379
vdb-entry
-
ics-cert.us-cert.gov
/advisories/ICSA-18-067-01
third-party-advisory, us-government-resource
Sources