CVE-2019-5172 json
An exploitable command injection vulnerability exists in the iocheckd service ‘I/O-Check’ function of the WAGO PFC 200 Firmware version 03.…
published 6y ago modified 4mo ago also EUVD-2019-14777
- cvss
- 7.8
- version 3.1, NVD
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 1.3%
- EPSS 1.3% chance of exploitation in 30 days, percentile 71%
- public exploits
- 0
- none known
Summary
An exploitable command injection vulnerability exists in the iocheckd service ‘I/O-Check’ function of the WAGO PFC 200 Firmware version 03.02.02(14). An attacker can send a specially crafted packet to trigger the parsing of this cache file. At 0x1e840 the extracted ntp value from the xml file is used as an argument to /etc/config-tools/config_sntp time-server-%d=<contents of ntp node> using sprintf(). This command is later executed via a call to system(). This is done in a loop and there is no limit to how many ntp entries will be parsed from the xml file.
Is CVE-2019-5172 in your stack? Fencer shows which of your repositories are affected as soon as an advisory lands, and opens the fix as a pull request.
Check with FencerExploit prediction
1.34% chance of exploitation in the next 30 days, higher than 71% of all scored CVEs (FIRST EPSS, 2026-11-09).
Exploits and checks
- talosintelligence.com https://talosintelligence.com/vulnerability_reports/TALOS-2019-0962 referenced PoC, tagged "exploit" by a source, unverified
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| NVD | 3.1 | 7.8 | CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H |
| NVD | 2.0 | 7.2 | AV:L/AC:L/Au:N/C:C/I:C/A:C |
Affected products
- Wago WAGO PFC200
Classification
- Weakness
-
- CWE-78 Improper Neutralization of Special Elements used in an OS Command
References
-
talosintelligence.com
/vulnerability_reports/TALOS-2019-0962
exploit, mitigation, technical-description, third-party-advisory
Sources
- CVE List CVE-2019-5172
- NVD CVE-2019-5172
Fencer Intel keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.