CVE-2020-27736 json
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions…
published 5y ago modified 4mo ago also EUVD-2020-20240
- cvss
- 6.5
- version 3.1, CNA
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 3.6%
- EPSS 3.6% chance of exploitation in 30 days, percentile 89%
- public exploits
- 0
- none known
Summary
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS domain name label parsing functionality does not properly validate the null-terminated name in DNS-responses. The parsing of malformed responses could result in a read past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition or leak the read memory.
Patch / fix
- siemens nucleus_readystart_v3 2017.02.3
- siemens nucleus_readystart_v4 4.1.0
- siemens simotics_connect_400_firmware 0.5.0.0
Is CVE-2020-27736 in your stack? Fencer shows which of your repositories are affected as soon as an advisory lands, and opens the fix as a pull request.
Check with FencerVendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-21-103-13 updated cvss 6.5
Siemens SIMOTICS CONNECT 400 (Update A)
-
Siemens SIMOTICS CONNECT 400 <V0.5.0.0affected: fixed in V0.5.0.0 support.industry.siemens.com
Facts from CISA's republication of the vendor's own advisory (CSAF); the linked advisory is the authoritative source. CISA notification · csaf
cisa ICSA-22-349-16 updated cvss 6.5
Siemens APOGEE and TALON
-
Siemens APOGEE PXC Compact (BACnet) <V3.5.5affected: fixed in V3.5.5 partnerportal.extranet.dc.siemens.com
-
Siemens APOGEE PXC Compact (P2 Ethernet) <V2.8.20affected: fixed in V2.8.20 partnerportal.extranet.dc.siemens.com
-
Siemens APOGEE PXC Modular (BACnet) <V3.5.5affected: fixed in V3.5.5 partnerportal.extranet.dc.siemens.com
-
Siemens APOGEE PXC Modular (P2 Ethernet) <V2.8.20affected: fixed in V2.8.20 partnerportal.extranet.dc.siemens.com
-
Siemens TALON TC Compact (BACnet) <V3.5.5 Siemens TALON TC Modular (BACnet) <V3.5.5affected: fixed in V3.5.5 partnerportal.extranet.dc.siemens.com
Facts from CISA's republication of the vendor's own advisory (CSAF); the linked advisory is the authoritative source. CISA notification · csaf
Exploit prediction
3.57% chance of exploitation in the next 30 days, higher than 89% of all scored CVEs (FIRST EPSS, 2026-11-09).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| CNA | 3.1 | 6.5 | CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:H/E:P/RL:O/RC:C |
| CNA | 3.1 | 6.5 | CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:H |
| NVD | 3.1 | 6.5 | CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:H |
| NVD | 2.0 | 5.8 | AV:N/AC:M/Au:N/C:P/I:N/A:P |
Affected products
- Siemens APOGEE PXC Compact (BACnet)
- Siemens APOGEE PXC Compact (P2 Ethernet)
- Siemens APOGEE PXC Modular (BACnet)
- Siemens APOGEE PXC Modular (P2 Ethernet)
- Siemens Nucleus NET
- Siemens Nucleus ReadyStart V3
- Siemens Nucleus ReadyStart V4
- Siemens Nucleus Source Code
- Siemens SIMOTICS CONNECT 400
- Siemens TALON TC Compact (BACnet)
- Siemens TALON TC Modular (BACnet)
Classification
References
-
cert-portal.siemens.com
/productcert/pdf/ssa-705111.pdf
patch, vendor-advisory
-
cert-portal.siemens.com
/productcert/pdf/ssa-669158.pdf
patch, vendor-advisory
- cert-portal.siemens.com /productcert/pdf/ssa-180579.pdf
Sources
- CVE List CVE-2020-27736
- NVD CVE-2020-27736
Fencer Intel keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.