Skip to content
Fencer Intel
medium 6.1

CVE-2020-7575 json

A vulnerability has been identified in Climatix POL908 (BACnet/IP module) (All versions), Climatix POL909 (AWM module) (All versions < V11.…

published 6y ago modified 4mo ago also EUVD-2020-28700

cvss
6.1
version 3.1, NVD
cisa kev
Not listed
not in CISA's catalog
epss
0.7%
EPSS 0.7% chance of exploitation in 30 days, percentile 51%
public exploits
0
none known

Summary

A vulnerability has been identified in Climatix POL908 (BACnet/IP module) (All versions), Climatix POL909 (AWM module) (All versions < V11.32). A persistent cross-site scripting (XSS) vulnerability exists in the web server access log page of the affected devices that could allow an attacker to inject arbitrary JavaScript code via specially crafted GET requests. The code could be potentially executed later by another (privileged) user. The security vulnerability could be exploited by an attacker with network access to the affected system. Successful exploitation requires no system privileges. An attacker could use the vulnerability to compromise the confidentiality and integrity of other users' web sessions.

Patch / fix

  • siemens climatix_pol909_firmware 11.32

Is CVE-2020-7575 in your stack? Fencer shows which of your repositories are affected as soon as an advisory lands, and opens the fix as a pull request.

Check with Fencer

Vendor advisories

What the vendors themselves say about their products: affected, fixed or not affected, and what to do.

cisa ICSA-20-105-04 updated cvss 6.1

Siemens Climatix (Update A)

  • Siemens Climatix POL908 (BACnet/IP module)
    affected: mitigation
  • Siemens Climatix POL909 (AWM module) <V11.32
    affected: fixed in V11.32, mitigation

Facts from CISA's republication of the vendor's own advisory (CSAF); the linked advisory is the authoritative source. CISA notification · csaf

Exploit prediction

0.66% chance of exploitation in the next 30 days, higher than 51% of all scored CVEs (FIRST EPSS, 2026-11-09).

CVSS scores

assigned by version score vector
NVD 3.1 6.1 CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N
NVD 2.0 4.3 AV:N/AC:M/Au:N/C:N/I:P/A:N

Affected products

  • Siemens Climatix POL908 (BACnet/IP module)
  • Siemens Climatix POL909 (AWM module)

Classification

Weakness
  • CWE-80 Improper Neutralization of Script-Related HTML Tags in a Web Page
  • CWE-79 Improper Neutralization of Input During Web Page Generation

References

Sources