Skip to content
Fencer Intel
medium 6.5

CVE-2022-2758 json

Update

published 4y ago modified 4mo ago also EUVD-2022-35000

cvss
6.5
version 3.1, CNA
cisa kev
Not listed
not in CISA's catalog
epss
0.4%
EPSS 0.4% chance of exploitation in 30 days, percentile 34%
public exploits
0
none known

Summary

Passwords are not adequately encrypted during the communication process between all versions of LS Industrial Systems (LSIS) Co. Ltd LS Electric XG5000 software prior to V4.0 and LS Electric PLCs: all versions of XGK-CPUU/H/A/S/E prior to V3.50, all versions of XGI-CPUU/UD/H/S/E prior to V3.20, all versions of XGR-CPUH prior to V1.80, all versions of XGB-XBMS prior to V3.00, all versions of XGB-XBCH prior to V1.90, and all versions of XGB-XECH prior to V1.30. This would allow an attacker to identify and decrypt the password of the affected PLCs by sniffing the PLC’s communication traffic.

Patch / fix

  • LS Industrial Systems (LSIS) Co. Ltd LS Electric XG5000 V4.0
  • LS Industrial Systems (LSIS) Co. Ltd LS Electric PLC: XGB-XECH V1.30
  • LS Industrial Systems (LSIS) Co. Ltd LS Electric PLC: XGB-XBCH V1.90
  • LS Industrial Systems (LSIS) Co. Ltd LS Electric PLC: XGB-XBMS V3.00
  • LS Industrial Systems (LSIS) Co. Ltd LS Electric PLC: XGR-CPUH V1.80
  • LS Industrial Systems (LSIS) Co. Ltd LS Electric PLC: XGI-CPUU/UD/H/S/E V3.20
  • LS Industrial Systems (LSIS) Co. Ltd LS Electric PLC: XGK-CPUU/H/A/S/E V3.50

Is CVE-2022-2758 in your stack? Fencer shows which of your repositories are affected as soon as an advisory lands, and opens the fix as a pull request.

Check with Fencer

Vendor advisories

What the vendors themselves say about their products: affected, fixed or not affected, and what to do.

cisa ICSA-22-228-02 updated cvss 7.5

LS ELECTRIC PLC and XG5000 (Update A)

  • LS ELECTRIC, LS Industrial Systems (LSIS) Co. Ltd XG5000 <V4.0
    affected: fixed in 4.0 ls-electric.com
  • LS ELECTRIC, LS Industrial Systems (LSIS) Co. Ltd XGB-XBCH <V1.90 LS ELECTRIC, LS Industrial Systems (LSIS) Co. Ltd XGB-XBMS <V3.00 LS ELECTRIC, LS Industrial Systems (LSIS) Co. Ltd XGB-XECH <V1.30 LS ELECTRIC, LS Industrial Systems (LSIS) Co. Ltd XGI-CPUU/UD/H/S/E <V3.20 LS ELECTRIC, LS Industrial Systems (LSIS) Co. Ltd XGK-CPUU/H/A/S/E <V3.50 LS ELECTRIC, LS Industrial Systems (LSIS) Co. Ltd XGR-CPUH <V1.80
    affected: vendor fix, mitigation “LS ELECTRIC PLC: Contact the LS ELECTRIC Technical Center (Worldwide or South Korea) to upgrade the firmware.” ls-electric.com

From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf

CISA SSVC

Exploitation
none
Automatable
no
Technical impact
partial
Assessed
last yr.

Exploit prediction

0.40% chance of exploitation in the next 30 days, higher than 34% of all scored CVEs (FIRST EPSS, 2026-11-09).

CVSS scores

assigned by version score vector
CNA 3.1 6.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N
NVD 3.1 5.9 CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N

Affected products

  • LS Industrial Systems (LSIS) Co. Ltd LS Electric XG5000
  • LS Industrial Systems (LSIS) Co. Ltd LS Electric PLC: XGB-XECH
  • LS Industrial Systems (LSIS) Co. Ltd LS Electric PLC: XGB-XBCH
  • LS Industrial Systems (LSIS) Co. Ltd LS Electric PLC: XGB-XBMS
  • LS Industrial Systems (LSIS) Co. Ltd LS Electric PLC: XGR-CPUH
  • LS Industrial Systems (LSIS) Co. Ltd LS Electric PLC: XGI-CPUU/UD/H/S/E
  • LS Industrial Systems (LSIS) Co. Ltd LS Electric PLC: XGK-CPUU/H/A/S/E

Classification

Weakness
  • CWE-326 Inadequate Encryption Strength

References

Sources

Fencer Intel keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.