The Emerson ControlWave 'Next Generation' RTUs through 2022-05-02 mishandle firmware integrity.
published 4y ago modified 4mo ago also EUVD-2022-52222
- cvss
- 7.8
- version 3.1, NVD
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 0.2%
- EPSS 0.2% chance of exploitation in 30 days, percentile 7%
- public exploits
- 0
- none known
Summary
The Emerson ControlWave 'Next Generation' RTUs through 2022-05-02 mishandle firmware integrity. They utilize the BSAP-IP protocol to transmit firmware updates. Firmware updates are supplied as CAB archive files containing a binary firmware image. In all cases, firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks.
Is CVE-2022-30262 in your stack? Fencer shows which of your repositories are affected as soon as an advisory lands, and opens the fix as a pull request.
Check with FencerVendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-22-221-02 updated cvss 9.1
Emerson ControlWave
-
Emerson ControlWaveaffected: vendor fix
From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf
Exploit prediction
0.18% chance of exploitation in the next 30 days, higher than 7% of all scored CVEs (FIRST EPSS, 2026-11-09).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| NVD | 3.1 | 7.8 | CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H |
Classification
- Weakness
-
- CWE-345 Insufficient Verification of Data Authenticity
References
-
forescout.com
/blog/
third-party-advisory
-
cisa.gov
/uscert/ics/advisories/icsa-22-221-02
mitigation, third-party-advisory, us-government-resource