CVE-2025-31353 json
A vulnerability has been identified in TeleControl Server Basic (All versions < V3.1.2.2).
published last yr. modified 4mo ago also EUVD-2025-11447
- cvss
- 8.8
- version 3.1, CNA
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 0.8%
- EPSS 0.8% chance of exploitation in 30 days, percentile 57%
- public exploits
- 0
- none known
Summary
A vulnerability has been identified in TeleControl Server Basic (All versions < V3.1.2.2). The affected application is vulnerable to SQL injection through the internally used 'UpdateOpcSettings' method. This could allow an authenticated remote attacker to bypass authorization controls, to read from and write to the application's database and execute code with "NT AUTHORITY\NetworkService" permissions. A successful attack requires the attacker to be able to access port 8000 on a system where a vulnerable version of the affected application is executed on. (ZDI-CAN-25916)
Patch / fix
- Siemens TeleControl Server Basic V3.1.2.2
Is CVE-2025-31353 in your stack? Fencer shows which of your repositories are affected as soon as an advisory lands, and opens the fix as a pull request.
Check with FencerVendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-25-112-01 updated cvss 8.8
Siemens TeleControl Server Basic SQL
-
Siemens TeleControl Server Basic <V3.1.2.2affected: fixed in V3.1.2.2, mitigation support.industry.siemens.com
Facts from CISA's republication of the vendor's own advisory (CSAF); the linked advisory is the authoritative source. CISA notification · csaf
CISA SSVC
- Exploitation
- none
- Automatable
- no
- Technical impact
- total
- Assessed
- last yr.
Exploit prediction
0.82% chance of exploitation in the next 30 days, higher than 57% of all scored CVEs (FIRST EPSS, 2026-11-09).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| CNA | 3.1 | 8.8 | CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H |
| CNA | 4.0 | 8.7 | CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N |
| CNA | 4.0 | 8.7 | CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X |
Affected products
- Siemens TeleControl Server Basic
Classification
- Weakness
-
- CWE-89 Improper Neutralization of Special Elements used in an SQL Command
References
-
cert-portal.siemens.com
/productcert/html/ssa-443402.html
vendor-advisory
Sources
- CVE List CVE-2025-31353
- NVD CVE-2025-31353
Fencer Intel keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.